Specifications
for Superconductor Current
Fault Limiter, 480 Volt Class, Model LX-4
Operating Voltage...............................................................
480 V, 3-phase
Operating Frequency.......................................................
60 Hz
Continuous Current..................................................................
600 amps
Fault Short Circuit Power ..........................................................
4.2MVA
Fault Limit Current.................................................................
5,000 A rms sym
Inductance Range .......................................................
100mH to 6.0
mH
I2
T Rating .....................................................................
2,075,000 amp-2 sec.
Operating Time to Limit Peak
.............................................
4.2 milliseconds
Enclosure ........................................................
Hermetically sealed, shielded
Insulation ................................................................
Class H, 50 kV BIL
Diameter Overall / Length ................................................
25 inch / 42 inch
Magnetics Weight .............................................................
205 lbs.
Wire Type .....................................
BSCCO-2223 Superconductor
Operating Temperature ....................................................
20oK
Internal Field .................................................................
1.5 Tesla
External Field at 1.0 m ........................................................
5 milli-Tesla
Total Reset Time ...............................................................
10 milliseconds
Compressor Supplier .........................................................
Cryomech Inc.
Refrigerator type ..................................
Two-stage, Gifford-McMahon refrig.
Weight ..........................................................................
370 lbs.
Capacity ........................................................................
15 watts at 20oK
Input Line Power .............................................................
5 kilowatts, 60 Hz
Total system weight incl. refrigeration
................................
575 lbs. (227 kg.)
Standard Ratings
of Cryo-PinchLimiters
Model
Voltage
Continuous Current (rms)
Short-Circuit Current
(A Sym)
LX-4
480
600
5,000
LX-5
5 kV
600
12,000
LX-6
7.5 kV
600
12,000
LX-7
7.6 kV
1200
28,000
LX-8
15 kV
600
12,000
LX-9
15 kV
1200
28,000
LX-10
23 kV
400
32,000
LX-11
38 kV
200
42,000
Related product from PSA: 8 MVAR
superconducting synchronous condense for
ultra-compact power factor compensation 5 kV, 925 amps.
POWER SUPERCONDUCTOR APPLICATIONS CORPORATION
930 Cass Street
New Castle, PA 16101
Laboratory Telephone: 724-652-8610 Office Telephone: 412-824-5062 E-Mail: psacorp@peoplepc.com